Configuration & Operation

Manual Documentation Number: ZXTx-IO-x-4113m

33

c. Channel Number range is different for 900 MHz and 2.4 GHz Zlinx Xtreme I/Os. The table below shows the ranges and

commands in hexadecimal values:

Type/Range

Xtreme Module

Channel Number

Range

Factory Default

ZXT24-IO-222R2

0x0C to 0x17

0x0C

ZXT9-IO-222R2

0x00 to 0x09

0x00

Fig 6-4 Channel Number Range

6.1.1.3 Network Identifier

a. The Network Identifier field must match the Network Identifier used by the device with which it will communicate.

b. If that device is another Zlinx Xtreme I/O Module, set its Network Identifier the same as the local I/O Module

c.

If that device is a Modbus Radio Modem, its Network Identifier must be configured by using the Radio Modem
Configuration Manager to match that of the I/O module. Refer Radio Modem manual for configuration information.

d. The Network Identifier range is different for both radio types (2.4 GHz and 900 MHz). The table below shows the channel

number ranges in hexadecimal values.

Type/Range

Xtreme Module Network

Identifier Range

Factory Default

ZXT24-IO-222R2

0x00 to 0xFF

0x00

ZXT9-IO-222R2

0x11 to 0xFF

0x11

Fig 6-5 Network Identifier Range

e. If the Network Identifier is changed to outside the default value, it must be matched in the other device as well.

6.1.1.4 Repeater Mode

a. Select the Repeater checkbox if the Zlinx Xtreme I/O Module is to be used as a repeater, re-broadcasting I/O data

received in Modbus or Peer-to-Peer modes.

The default value of the Repeater field is unchecked.

6.1.1.5 RF Data Rate

900 MHz Xtreme Modules allow you to configure the over-the-air RF Data Rate. Using 9600 baud on these modules
increases the effective range of the module.

This data rate may be configured for 9600 baud or 115200 baud.

NOTE: Repeater Mode can only be implemented on the ZXT9-IO-222R2 Xtreme I/O Modules.