2 voltage display, 3 status indicator, Table 3-1. description of status indicators – American Magnetics 05100PS-430-601 Integrated Power Supply System User Manual
Page 44: Table 3-1, Description of status indicators, Operation
26
Rev. 5
Operation
Default Display : Voltage
Note
Note that the displayed field strength is not directly measured, but
rather is calculated by multiplying the coil constant entered in the
setup menu by the measured current flow of the Model 430 power
supply system.
3.2.2 Voltage
Display
The voltage display indicates either the voltage across the magnet (Vm) or
the power supply output voltage (Vs). This is always displayed in the lower
left corner of the display (see Figure 3-1), regardless of what else is being
displayed on the Model 430 Programmer display. The parameter displayed
(magnet voltage or power supply voltage) is toggled by pressing
SHIFT
followed by
Vs <> Vm
. Vm indicates the voltage measured across the
terminals of the connected superconducting magnet. In order for the Model
430 Programmer to measure the magnet voltage, the magnet voltage taps
must be connected to the Model 430. Normally this is done through the
Magnet Station Cable provided by AMI (if the whole magnet system is
provided by AMI). Vs indicates the Model 430 Programmer-controlled
power supply output voltage.
Note
Note that the displayed power supply voltage (Vs) is not directly
measured, but rather is calculated based on power supply control
voltage being provided by the Model 430 Programmer and the power
supply input control voltage and output voltage values entered in
the setup menu.
3.2.3 Status
Indicator
The status indicator indicates the
Model 430 Programmer operating
status. It is always visible (except
during a quench condition) and is
displayed just to the right of the
field / current display (see Figure
3-1). The status indicator may be
one of six symbols indicating one
of the seven states shown in Table
If the ramping mode character is
blank, then a quench condition
exists and the red MAGNET
QUENCH indicator in the status
section of the front panel will be
illuminated. See section 3.12 on page 77 for a detailed discussion of the
Table 3-1.
Description of
Status Indicators
P
Paused
Ramping Up
Ramping Down
–
Holding
Heating Persistent Switch
Cooling Persistent Switch
V
Voltage Limit