40 Ton

T

Note:
1. Fan curves include refrigerant coil and internal cabinet

static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.

Table PD-49. SCRF/SIRF 40 Gross Cooling Capacity - 18,400 cfm

Entering Ambient Air Temperature

75 F

85 F

95 F

105 F

115 F

EDB EWB

Tot

Sen

Tot

Sen

Tot

Sen

Tot

Sen

Tot

Sen

F

F

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

70

62

512.1

343.9

493.5

335.8

473.8

327.2

452.9

318.3

430.8

308.9

67

559.2

249.9

539.0

241.9

517.6

233.6

495.0

224.8

471.1

215.7

62

512.3

434.1

494.0

425.8

474.6

417.0

454.1

407.6

432.6

397.5

75

67

558.7

339.8

538.5

331.8

517.2

323.4

494.6

314.6

470.7

305.4

72

608.7

245.2

586.8

237.4

563.6

229.2

539.0

220.7

513.2

211.8

62

522.3

509.6

505.7

496.5

488.0

482.5

469.3

467.3

449.8

450.1

80

67

558.2

429.4

538.1

421.3

516.9

412.9

494.5

404.0

470.9

394.6

72

608.2

334.4

586.3

326.6

563.1

318.4

538.6

309.8

512.8

300.8

62

548.1

548.2

532.0

532.0

514.7

514.8

496.2

496.3

476.6

476.6

85

67

561.3

516.7

542.0

507.6

521.9

497.2

501.4

483.4

480.1

467.3

72

607.7

423.4

585.8

415.5

562.6

407.2

538.1

398.5

512.4

389.5

Chart PD-65. SCRF/SIRF 40 Fan Performance for CV or with VFD

Chart PD-66. SCRF/SIRF 40 Fan Performance with Inlet Guide Vanes