Performance water-cooled data, 38 ton – Trane PKG-PRC002-EN User Manual

Page 45

background image

Performance

Water-Cooled

Data

PKG-PRC002-EN

45

38 Ton

Note:
1. Fan curves include refrigerant coil and internal cabinet

static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.

Table PD-22. SCWF/SIWF 38 Gross Cooling Capacity - 15,200 cfm, 114 gpm

Entering Water Temp

Entering Air

75 F

85 F

95 F

EDB

EWB

Total

Sensible

Total

Sensible

Total

Sensible

F

F

MBh

MBh

LWT

MBh

MBh

LWT

MBh

MBh

LWT

62

434

373

83.9

416

365

93.8

398

357

103.7

75

67

471

290

84.6

452

283

94.5

432

275

104.3

72

511

206

85.3

490

199

95.2

469

192

105.0

62

441

441

84.1

426

426

94.0

410

410

103.9

80

67

470

369

84.6

452

361

94.5

432

353

104.3

72

510

285

85.3

490

277

95.2

468

270

105.0

62

465

465

84.5

450

450

94.4

433

433

104.4

85

67

473

444

84.7

455

435

94.5

436

425

104.4

72

510

363

85.3

489

355

95.2

468

348

105.0

Chart PD-39. SCWF/SIWF 38 Fan Performance for CV or with VFD

Chart PD-40. SCWF/SIWF 38 Fan Performance with Inlet Guide Vanes