Performance water-cooled data, 80 ton – Trane PKG-PRC002-EN User Manual

Page 59

background image

Performance

Water-Cooled

Data

PKG-PRC002-EN

59

80 Ton

Note:
1. Fan curves include refrigerant coil and internal cabinet

static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.

Table PD-43. SCWF/SIWF 80 Gross Cooling Capacity - 29,800 cfm, 240 gpm

Entering Water Temp

Entering Air

75 F

85 F

95 F

EDB

EWB

Total

Sensible

Total

Sensible

Total

Sensible

F

F

MBh

MBh

LWT

MBh

MBh

LWT

MBh

MBh

LWT

62

891

761

83.7

856

746

93.6

819

729

103.4

75

67

966

590

84.3

928

575

94.2

887

559

104.0

72

1049

419

85.0

1007

405

94.8

963

389

104.7

62

910

896

83.8

880

867

93.8

847

834

103.7

80

67

967

752

84.3

929

737

94.2

888

721

104.0

72

1048

579

85.0

1006

565

94.8

963

550

104.7

62

961

947

84.3

930

916

94.2

896

883

104.1

85

67

975

908

84.4

938

890

94.3

899

871

104.1

72

1047

740

85.0

1006

725

94.8

963

710

104.7

Chart PD-53. SCWF/SIWF 80 Fan Performance for CV or with VFD

Chart PD-54. SCWF/SIWF 80 Fan Performance with Inlet Guide Vanes