Air-cooled units, Performance air-cooled data, 20 ton – Trane PKG-PRC002-EN User Manual

Page 60

background image

Performance

Air-Cooled

Data

PKG-PRC002-EN

60

20 Ton

Note:
1. Fan curves include refrigerant coil and internal cabinet

static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.

Table PD-44. SCRF/SIRF 20 Gross Cooling Capacity - 10,000 cfm - Air Cooled

Entering Ambient Air Temperature

75 F

85 F

95 F

105 F

115 F

EDB EWB

Tot

Sen

Tot

Sen

Tot

Sen

Tot

Sen

Tot

Sen

F

F

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

MBh

70

62

287.5

191.1

277.4

186.6

266.5

181.9

255.0

176.9

242.6

171.7

67

313.6

139.5

302.6

135.2

290.9

130.6

278.4

125.7

265.1

120.6

62

287.3

240.4

277.4

235.9

266.8

231.1

255.4

226.0

243.4

220.5

75

67

313.3

188.7

302.4

184.3

290.7

179.7

278.2

174.8

264.9

169.7

72

341.1

136.8

329.2

132.5

316.5

128.1

303.0

123.3

288.7

118.4

62

291.4

286.6

282.3

280.6

272.9

273.1

263.2

263.3

252.7

252.7

80

67

313.1

237.6

302.1

233.2

290.4

228.6

278.0

223.7

264.8

218.5

72

340.8

185.6

328.9

181.3

316.2

176.8

302.7

172.0

288.4

167.1

62

306.9

306.9

298.1

298.2

288.7

288.7

278.5

278.6

267.6

267.7

85

67

314.5

285.8

303.9

281.1

292.7

275.9

280.9

270.2

268.5

263.6

72

340.5

234.2

328.6

229.9

316.0

225.3

302.5

220.5

288.2

215.5

Chart PD-55. SCRF/SIRF 20 Fan Performance for CV or with VFD

Chart PD-56. SCRF/SIRF 20 Fan Performance with Inlet Guide Vanes