Performance water-cooled data, 42 ton – Trane PKG-PRC002-EN User Manual

Page 47

background image

Performance

Water-Cooled

Data

PKG-PRC002-EN

47

42 Ton

Note:
1. Fan curves include refrigerant coil and internal cabinet

static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to external
duct static pressure.

Table PD-25. SCWF/SIWF 42 Gross Cooling Capacity - 16,800 cfm, 126 gpm

Entering Water Temp

Entering Air

75 F

85 F

95 F

EDB

EWB

Total

Sensible

Total

Sensible

Total

Sensible

F

F

MBh

MBh

LWT

MBh

MBh

LWT

MBh

MBh

LWT

62

488

403

84.1

469

394

94.1

449

385

104.0

75

67

530

317

84.9

510

309

94.7

488

300

104.6

72

576

231

85.6

554

223

95.5

531

215

105.3

62

493

473

84.3

476

460

94.2

458

445

104.1

80

67

530

397

84.9

510

389

94.7

488

380

104.6

72

576

311

85.6

554

303

95.5

530

295

105.3

62

513

512

84.6

496

496

94.5

479

479

104.5

85

67

532

476

84.9

512

467

94.8

491

456

104.6

72

575

391

85.6

553

383

95.5

530

375

105.3

Chart PD-41. SCWF/SIWF 42 Fan Performance for CV or with VFD

Chart PD-42. SCWF/SIWF 42 Fan Performance with Inlet Guide Vanes