S3200-h – Omron CQM1H-CLK21 User Manual
Page 97
![background image](/manuals/206827/97/background.png)
74
Wiring
Section 3-3
Communications Cables
Optical Bus or Optical
Ring System (H-PCF
Cable)
The following devices are required for the Optical Bus or Optical Ring (H-PCF)
Controller Link Network. The cable and connectors are the same as those
used for Optical SYSMAC LINK Networks.
Optical Fiber Cables (Indoor Use Only)
Use the following Optical Fiber Cables (Hard Plastic-clad Fiber: H-PCF).
Note The Optical Fiber Cable model numbers are as follows.
Note
1.
Either full-lock or half-lock connectors can be used in a Controller Link Net-
work, but we recommend full-lock connectors to prevent accidental discon-
nections during operation.
2.
The maximum distance between nodes is slightly shorter for connectors
with crimp-cut cables compared to connectors assembled with adhesive.
Also, the maximum distance is reduced due to extension loss when Inline
Adapters are used to extend cables.
Name
Specifications
Model
H-PCF cables
Black
10 m
S3200-HCCB101
50 m
S3200-HCCB501
100 m
S3200-HCCB102
500 m
S3200-HCCB502
1,000 m
S3200-HCCB103
Orange
10 m
S3200-HCCO101
50 m
S3200-HCCO501
100 m
S3200-HCCO102
500 m
S3200-HCCO502
1,000 m
S3200-HCCO103
Name
Model
Specifications
Connector
S3200-COCF2071
Use to connect a cable to a node.
(Full-lock connector for crimp-cut cable.)
S3200-COCF2571
Use to connect a cable to a node.
(Half-lock connector for crimp-cut cable.)
Inline Adapter
S3200-COIAT2000
Use to connect or extend cables.
(Use one adapter for each connection.)
S3200-H
@@@@@@@
Tensioner option
None: Standard (with tension member)
N: Without tension member
Cable length
@@@
A B
(A/10) x 10
B
m
Cable color
B:
Black
O: Orange
Cable specification
L:
With power supply line
C:
Without power supply line
Type
B:
Cord
C:
Cable