P.45 and – Omron CQM1H-CLK21 User Manual
Page 68
45
Component Names and Functions
Section 3-1
Wired Unit Indicators
Note Even when the local node does not participate in the data link, the
indicator will be lit if there are manually set data links active on the
network.
9-1 Troubleshooting Using Indicators
Name
Color
Status
Meaning
RUN
(operating)
Green
Lit
Unit operating normally.
Not lit
Unit error.
ERC (communica-
tions error)
Red
Lit
Communications error, node address
setting error (same address set twice), or
hardware error.
Not lit
Normal operation
ERH
(PLC error)
Red
Lit
PLC error, PLC interface error, EEPROM
error, unit number error, or I/O table not
set
Not lit
No error.
INS
(network participa-
tion)
Yellow
Lit
Unit is participating (inserted) in the net-
work.
Not lit
Unit is not participating (inserted) in the
network.
SD
(send)
Yellow
Lit
Data transmission.
Not lit
No data transmission.
RD
(receive)
Yellow
Lit
Data reception.
Not lit
No data reception.
M/A
(data link mode)
Yellow
Lit
Manual
(see note)
Note:
M/A is always not lit
when data links are not
active in the network.
Not lit
Automatic
LNK
(data link)
Yellow
Lit
Data links participating.
Flashing
Error in data link table.
Not lit
Not in a data link or data link inactive.
TER
(terminating resis-
tance)
Yellow
Lit
Terminating resistance switch ON.
Not lit
Terminating resistance switch OFF.