2-5 devices for connection, Devices for connection, Communications cables – Omron CQM1H-CLK21 User Manual
Page 42: Repeater units (when required)
19
Specifications and Configurations
Section 1-2
1-2-5
Devices for Connection
To set up a Controller Link Network, the following devices are needed in addi-
tion to a Controller Link Unit and a PLC.
Communications Cables
The following shielded twisted-pair cables are recommended for Wired Con-
troller Link Network connections.
Note Use the special connector provided with the Board to connect the Controller
Link Support Board to the network.
Repeater Units (when Required)
The following Repeater Units can be used to facilitate the use of T-Branch wir-
ing, long-distance wiring, and the addition or removal of nodes.
Three types of Repeater Unit are available for use with different transmission
line types (i.e., connection methods).
Model
Manufacturer
Remarks
Li2Y-FCY2 x 0.56 qmm
Kromberg & Schubert,
Komtec Department
German company
1 x 2 x AWG
–
20PE +
Tr.CUSN + PVC
Draka Cables Industrial
Spanish company
#9207
Belden
USA company
ESVC 0.5 x 2 C-1362
Bando Densen Co.
Japanese company
ESNC 0.5 x 2 C-99-087B
Nihon Electric Wire &
Cable Co.
Japanese company
Item
Specifications
Model
CS1W-RPT01
CS1W-RPT02
CS1W-RPT03
External appearance
Supported Units/
Boards
All Controller Link Units/Boards for wired networks.
Note
To construct a network that can contain up to 62 nodes, it is necessary to use version-1
models, which support 62 nodes.
Transmission line
Twisted-pair cable
H-PCF cable (optical
two-core cable)
GI cable (optical two-
core cable; 62.5/125
µ
m,
50/125
µ
m)