beautypg.com

7 response codes, 7-1 configuration, Response codes – Omron CQM1H-CLK21 User Manual

Page 248: Configuration

background image

225

Response Codes

Section 6-7

IR, SR, LR, HR, and AR Areas:

Timers/Counters: Status of the Completion Flag will be returned as fol-
lows:

00 (Hex): No forced status in effect
01 (Hex): Forced ON or forced OFF

6-7

Response Codes

This section describes the response codes returned with responses to FINS
commands. Response codes can be used to confirm normal completion of
command execution or to troubleshoot problems when commands fail. For fur-
ther troubleshooting information, refer to SECTION 9 Troubleshooting and
Maintenance
of this manual and to the operation manuals for specific Units or
Systems.

6-7-1

Configuration

Response codes for FINS commands consist of two bytes that indicate the
result of executing a command. The structure of the response codes is shown
in the following diagram.

The main response code (MRES) in the first byte classifies the response and
the sub-response code (SRES) in the second byte indicates details under the
MRES classification.

If bit 7 of the first byte is ON, a network relay error has occurred. Refer to 6-7-
2 Network Relay Errors
for details on troubleshooting the error.

If bit 6 or 7 of the second byte is ON, an error has occurred in the PLC or com-
puter returning the response. Refer to the operation manual for the device
returning the response for details when troubleshooting the error.

Bit 0

15

14 13

12 11

10

9

8

7

6

5

4

3

2

1

0

Bit

Bit 1

Bit 2

Bit 4

Bit 6

Bit 8

Bit 10

Bit 12

Bit 14

Bit 3

Bit 5

Bit 9

Bit 7

Bit 11

Bit 13

Bit 15

The status for each bit is as follows:
OFF (0): No forced status in effect
ON (1): Forced ON or forced OFF

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Bit

1: PLC Non-fatal Error Flag

1: PLC Fatal Error Flag

1: Relay Error Flag

First byte

Second byte

Main response code (MRES)

Sub-response code (SRES)