Data Link I/O Response Time

Section 8-3

There are three points shown in the diagram above where processing is
delayed, increasing the data link I/O response time.

1,2,3...

1.

The input arrives in the PLC just after I/O refreshing, causing a delay of up
to one cycle before the input is read into the PLC.

2.

Data exchange occurs just after the PLC at node #1 passes the token that
makes it the polling node, causing a delay of up to one communications cy-
cle time before the data is transferred in data link processing.

3.

The data transferred in data link processing arrives at the PLC at node #7
after data exchange, so the data will not be read into the PLC until the next
data exchange, causing a delay of up to 1 to 2 cycle.

The maximum number of words that can be exchanged in a single data ex-
change is approx. 7,800 words for CS/CJ-series PLCs, approx. 3,700
words for CVM1 and CV-series PLCs, approx. 4,000 for C200HX/HG/HE
PLCs, and approx. 1,200 words for CQM1H-series PLCs.

The equation for maximum data link I/O response time is as follows:

Note If the total number of data link words is greater than the maximum number of

words that can be exchanged per data exchange, the maximum data link I/O
response time will be cycle time of PLC at node #7

×

3.

In case of the CQM1H, however, the cycle time will be incremented by the
value obtained from dividing the total number of data link words by the maxi-

Input device

Program

Program

Input

Input ON delay

1 cycle

Output

Output device

Output ON
delay

1 cycle

Communications
cycle time

Data link transmission

Controller Link Unit
transmission processing

PLC at node #7

(1)

I/O refresh

Data exchange

Controller Link Unit
transmission processing

PLC at node #1

Data link I/O response time

X

X

(2)

(3)

X

Input ON delay

1.5 ms

Cycle time of PLC at node #1

×

2

15 ms

×

2

Communications cycle time

×

3

9.9 ms

×

3

PLC cycle time at node #7

×

2 (See note.) 8 ms

×

2 (See note.)

Output ON delay

15 ms

Total (data link I/O response time)

92.2 ms