beautypg.com

6-1 command codes, 6-2 memory area designations, Command codes – Omron CQM1H-CLK21 User Manual

Page 235: Memory area designations

background image

212

Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs

Section 6-6

6-6

Commands and Responses for C200HX/HG/HE and
CQM1H-series PLCs

6-6-1

Command Codes

6-6-2

Memory Area Designations

The following table gives the addresses to use when reading or writing PLC
data. The Data area address column gives the normal addresses used in the
PLC program. The Address used in communications column are the
addresses used in CV-mode commands and responses. These addresses
are combined with the memory area codes to specify PLC memory locations.
These addresses are not the same as the actual memory addresses of the
data.

The No. of bytes column specifies the number of bytes to read or write data for
that area. The number of bytes varies for the same area depending on the
memory area code. Actual data area sizes vary with the PLC being used.
Refer to your PLC’s operation manual for specific limits.

Command

code

PLC mode

Name

Page

RUN

MONITOR

PROGRAM

01

01

Valid

Valid

Valid

MEMORY AREA READ

214

02

Valid

Valid

Valid

MEMORY AREA WRITE

215

04

Valid

Valid

Valid

MULTIPLE MEMORY AREA READ

216

03

06

Valid

Valid

Valid

PROGRAM AREA READ

216

07

Not valid

Not valid

Valid

PROGRAM AREA WRITE

217

04

01

Valid

Valid

Valid

RUN

218

02

Valid

Valid

Valid

STOP

218

05

01

Valid

Valid

Valid

CONTROLLER DATA READ

219

06

01

Valid

Valid

Valid

CONTROLLER STATUS READ

220

07

01

Valid

Valid

Valid

CLOCK READ

221

02

Not valid

Valid

Valid

CLOCK WRITE

221

21

01

Valid

Valid

Valid

ERROR CLEAR

222

23

01

Not valid

Valid

Valid

FORCED SET/RESET

222

02

Not valid

Valid

Valid

FORCED SET/RESET CANCEL

223

0A

Valid

Valid

Valid

MULTIPLE FORCED STATUS READ

224

Memory area

Data

Data area address

Address used in

communications

Memory

area code

No. of

bytes

1st and 2nd

bytes

3rd byte

IR Area 1, 2
SR Area 1, 2

Bit status

00000 to 51115

0000 to 01FF

00 to 0F

00

1

Word contents

000 to 511

00 to 00

80

2

LR Area

Bit status

LR 0000 to LR 6315

03E8 to 0427

00 to 0F

00

1

Word contents

LR 00 to LR 63

00 to 00

80

2

HR Area

Bit status

HR 0000 to HR 9915

0428 to 048B

00 to 0F

00

1

Word contents

HR 00 to HR 99

00 to 00

80

2

AR Area

Bit status

AR 0000 to AR 2715

048C to 04A7

00 to 0F

00

1

Word contents

AR 000 to AR 27

00 to 00

80

2

Timer/
Counter Area

Status

T/C 000
to T/C 511

0000 to 01FF

00 to 00

01

1

PV

81

2