3-3 using fins commands, Using fins commands – Omron CQM1H-CLK21 User Manual
Page 178
155
Starting and Stopping Data Links
Section 5-3
CVM1 and CV-series Start Bit
CQM1H-series Start Bit
5-3-2
Using the Controller Link Support Software and CX-Programmer
Data links can be started or stopped using commands on the Data Link Menu
of the Controller Link Support Software. The node for which starting and stop-
ping is being specified must participate in the data links.
Using a Programming Device Connected to PLC Node
Using a Computer Node
Data links can be started or stopped from the Controller Link Support Board
on the local node.
5-3-3
Using FINS Commands
Data links can be started and stopped by sending the RUN and STOP FINS
commands from a node on the Controller Link to a node that is in the data
links.
Issuing the FINS Command from a Computer Node
Data link Start Bit
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Word N
N: DM 2000 + 100
×
(unit number)
Data link Start Bit
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
AR 07
Node in data links
Start/stop data links
Controller Link Support Software or
CX-Net (in CX-Programmer)
IBM PC/AT or
compatible
Note The Controller Link Support Software cannot be connected to a CS-series PLC.
Use the CX-Net (in CX-Programmer).
Node in data links
IBM PC/AT or
compatible
Controller Link
Support Board
Start/stop data links
Controller Link
Support Software
FINS command:
RUN/STOP
Controller Link
Support Board
IBM PC/AT or
compatible
Node in data links