beautypg.com

6-16 forced set/reset cancel, Forced set/reset cancel – Omron CQM1H-CLK21 User Manual

Page 246

background image

223

Commands and Responses for C200HX/HG/HE and CQM1H-series PLCs

Section 6-6

Command Block

Response Block

Parameters

No. of bits/flags (command): The number of bits/flags to be processed.

Note Multiple bits/flags can be forced set/reset, and the status will be retained until

the forced set/reset is cleared.

Set/Reset specification (command): The action to be taken for each bit/flag:

Note “Forced status” is the ON/OFF status of bits/flags which is forcibly retained as

write protected.

Memory area code (command): The memory area of the bit or flag to be
controlled.

Bit/Flag (command): The bit or flag to be controlled.

Memory Areas
Refer to 6-6-2 Memory Area Designations for memory area designations.

6-6-16 FORCED SET/RESET CANCEL

Cancels the forced status of all bits/flags that have been forced ON or forced
OFF. (“Forced status” is the ON/OFF status of bits/flags which has been forc-
ibly retained as write protected.)

Command Block

Command

code

23

01

No. of

bits/flags

Bit/flag

Set/Reset

specification

Forced set/reset data

Memory area code

Set/reset

specification

Memory area code

Bit/flag

Forced set/reset data

Command

code

23

01

Response

code

Value

Function

0000 (Hex)

Force-reset (OFF)

0001 (Hex)

Force-set (ON)

8000 (Hex)

Forced status released and bit/flag turned OFF (0).

8001 (Hex)

Forced status released and bit/flag turned ON (1).

FFFF (Hex)

Forced status released.

Memory area

Data

IR, SR, LR, HR, and AR areas

Bits status

00

Timer/Counter

Completion Flag status

01

Command

code

23

02

This manual is related to the following products: