Setting Data Links

Section 5-2

Words N+22 through N+25 register nodes that will participate in the data
links. The numbers in the table are the node addresses. The bit status given
for each node address indicates whether the node is to participate in the data
links.

Participate: ON
Not participate: OFF

Note

1.

Leave the reserved words set to 0 (N+18 to N+20).

2.

When using automatic data link creation with 1:N allocations, set DM Pa-
rameter Area words N+2 to N+11 (which were previously used for automat-
ic setting with equality layout) to 0.

Setting Ranges for
Automatic Creation with
1:N allocations, 1 to 1
Type

15

8

7

0

N+12

---

N+13

N+14

(1)

N+15

(2)

N+16

(3)

N+17

(4)

N+18

---

N+19

---

N+20

---

N+21

---

N+22

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

N+23

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

N+24

48

47

46

45

44

43

42

41

40

39

38

37

36

35

34

33

N+25

---

---

62

61

60

59

58

57

56

55

54

53

52

51

50

49

(5)

1:N allocation type setting (Set value 0002 = 1 to 1 type)

Rightmost 4 digits of start word (BCD)

Area

Number of common send words for master node (BCD)

Number of individual send words for master node (BCD)

Number of send words for slave nodes (BCD)

0000 (Reserved)

0000 (Reserved)

0000 (Reserved)

First word to store data link status (bit-access area) (BCD)

Leftmost digit of area start word (BCD)

Item

Setting range

Data link mode

Specify automatic data link creation with 1:N allocations.

1:N allocation

Specify 1 to 1 type.

Area start word

Set the word address in BCD.

IR or CIO Area: 0 to 6143

LR Area: LR 000 to LR 199 (1000 to 1199) (See note.)

DM Area: D00000 to D32767

EM Area: Banks 0 to 12 E00000 to E32767

Note: When a word between LR 000 and LR 199 is spec-
ified, the data link area will be allocated between words
1000 and 1199 in the IR or CIO Area.

Area type

Set the area type of area 1 as a hexadecimal number.

IR Area: 80 Hex

LR Area: 86 Hex

DM Area: 82 Hex

EM Area Banks 0 to 7: 90 to 97 Hex

Banks 8 to 12: A8 to AC Hex

This manual is related to the following products: