beautypg.com

1 troubleshooting using indicators, 1-1 cs/cj-series controller link units, Troubleshooting using indicators – Omron CQM1H-CLK21 User Manual

Page 299: Cs/cj-series controller link units

background image

276

Troubleshooting Using Indicators

Section 9-1

9-1

Troubleshooting Using Indicators

This section describes the errors indicated by the Controller Link Unit indica-
tors and possible remedies.

9-1-1

CS/CJ-series Controller Link Units

Troubleshooting with RUN, ERC, ERH and INS Indicators

The RUN, ERC, ERH, and INS indicators can be used to check whether Con-
troller Link Unit startup and Network participation are operating normally.

Note Be sure to turn off the power to the PLC before performing any of the follow-

ing.

• Disconnecting the Unit or connectors.

• Securing Units or connectors.

• Setting hardware switches.

RUN: Operating
ERC: Communications

error

ERH: PLC

error

INS: Network

participation

LNK: Data

link

M/A: Data

link

mode

TER: Terminating

resistance

CS-series Unit

CJ-series Unit

RUN
ERC
INS
SD

RD

M/A
LNK

ERH

CLK21-V1

TER

RUN

CLK21-V1

ERC

INS

ERH M/A LNK

RD

TER

SD

Indicators

Probable cause

Probable remedy

RUN

ERC

ERH

INS

Lit

Not lit Not lit Lit

Unit operating normally;
Network participation nor-
mal.

---

Not lit Lit

---

---

Node address is set out of
range.

Set the node addresses to
between 1 and 32.

Controller Link Unit faulty.

If the ERC indicators still
lights when the Unit is
mounted on another PLC,
replace the Controller Link
Unit.

Wired Network 62 Node
Enable Bit is set incor-
rectly.

Turn ON the Wired Net-
work 62 Node Enable Bit
and turn the power supply
OFF and ON.

This manual is related to the following products: