Status Area and Troubleshooting

Section 9-2

Polling Node Address, Startup Node Address: IR 191

Network Participation Status: IR 192 and IR 193

Local Data Link Participation Status: IR 90

Note Data link status is valid only when the local node is participating in the data

link. Confirm that the Local Data Link Active Bit is ON before referencing the
data link status.

Data Link Status: IR 91 to
IR 93

When the first data link status word is not set or is set to the default (0000) for
either the manually set data link tables or automatically set data link tables,
the data link status is stored in the following words for nodes 1 to 6 only.

Note Refer to 5-4 Checking Data Link Status for details on status flags.

Polling node address

Startup node address

Each node address is displayed in 2-digit BCD.

The numbers in the squares indicate node addresses.
The corresponding node participation status is as follows:
0: Not part of the network
1: Part of the network

IR 192
IR 193

1: Local node data link participating
0: Local node data link not participating or data link

inactive

Node 2
Node 4
Node 6

Node 1
Node 3
Node 5

IR 91
IR 92
IR 93

PLC status
0: Inactive (user program not running)
1: Active (user program running)

Communications error (data link reception)
0: Normal
1: Error

PLC's CPU Unit error
0: Normal
1: Error

Data link participation
0: Not in data link or data link inactive
1: In data link

Offset error
0: Normal
1: Error

Error: Offset exceeds
number of send words.

Insufficient (short) receive area
0: Sufficient
1: Insufficient

Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.

Remaining receive area
0: Not remaining
1: Remaining

Remaining: Receive
area is larger than send
area. Data is received
and remaining words
are cleared.