beautypg.com

Omron CQM1H-CLK21 User Manual

Page 342

background image

319

Error Log

Section 9-3

Note

1.

Applicable PLCs: CV = CVM1 and CV-series PLCs, CS/CJ = CS-series
and CJ-series PLCs, All = All models of PLC.

2.

Errors indicated by error codes 0101 to 0116 are recorded only when the
frame was discarded because transmission was impossible.

3.

Error code 0230 hex is only recorded for Controller Link Units with unit ver-
sion 1.2 or later.

0216
Hex

Backup power supply error (Opti-
cal Units only)

00 Hex

Backup
power sup-
ply error dis-
tinction:
01 Hex:
OFF to ON
02 Hex: ON
to OFF

Check the status of
the backup power
supply and power
supply cables.

No

CS/CJ

021A
Hex

Set table logic error

00 Hex

01 Hex: Net-
work param-
eters
02 Hex:
Data link
tables
03 Hex:
Routing
tables

Remake and set the
appropriate data.

Check the unit ver-
sion.

Yes

All

021B
Hex

Hardware error

00 Hex

Error status
(See note.)

Replace the Control-
ler Link Unit.

No

All

021C
Hex

Data link error inactive

Not set

Restart the Control-
ler Link Unit.

Yes

All

0220
Hex

Reduced number of participating
nodes (separated nodes)

Separated nodes 1 to 16
correspond to bits 0 to 15
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)

Check the node
parameters, the sep-
arated nodes,
cables, and terminat-
ing resistance set-
tings.

No

CS/CJ

0221
Hex

Separated nodes 17 to 32
correspond to bits 0 to 15
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)

0222
Hex

Separated nodes 33 to 48
correspond to bits 0 to 15
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)

0223
Hex

Separated nodes 49 to 62
correspond to bits 0 to 13
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)

0230
Hex

Data link stop requested

Start node
address

Stop node
address

Check the applica-
tion and Support
Software operation if
the data link was not
intentionally stopped.

Yes

CS/CJ

0300
Hex

Packet discarded

Not set

Conduct an echo-
back test and find the
cause of the error.

No

All

0601
Hex

Unit error

Not set

Check the operating
environment.

Yes

All

Error

code

Contents

Detail code

Correction

Written to

EEPROM

Applicable

PLC

1st byte