beautypg.com

Omron CQM1H-CLK21 User Manual

Page 59

background image

36

Data Links Procedures

Section 2-1

Note a) When using fewer than 33 nodes, make sure that the Wired Net-

work 62 Node Enable Bit if the DM Parameter Area software
switch is turned OFF to restrict the network to 32 nodes maximum.
To construct a network containing more than 32 nodes, all nodes
must use the CS1W-CLK21-V1 or CJ1W-CLK21-V1.

b) Be sure that the data link mode in the data link parameters in the

DM Area is set to 00 when using manually set data links.

c) When using the 8-bit storage format, make sure that the relevant

locations in the DM Parameter Area are set to 0. The storage for-
mat used by all models other than CS1W-CLK21-V1, CS1W-
CLK21, CJ1W-CLK21-V1, and CJ1W-CLK21 is fixed at 8-bit, re-
gardless of the setting.

7.

Set the parameters for automatic data link creation.

• Equality layout: Previous automatic creation method (Compatible with

CS1W-CLK21-V1, CJ1W-CLK21-V1, CS1W-CLK21, CJ1W-CLK21,
C200HW-CLK21, CVM1-CLK21, and CQM1H-CLK21)

Contents

Method

Nodes

Page

a. Set the data link mode

to automatic.

Use the Support
Software or Pro-
gramming Console.

Data link startup node
only

The node that is used
to start the data link is
called the startup
node. It is necessary
to decide beforehand
which node will be
the startup node.

113

Area
1

b. Set the area

Data link startup node
only

Only when Area 1 is
used

130

c. Set the data

link start word

d. Set the num-

ber of data link
words

Area
2

e. Set the area

Data link startup node
only

Only when Area 2 is
used

f. Set the data

link start word

g. Set the num-

ber of data link
words

h. Set the first data link

status word

Data link startup node
only

(This setting may be
omitted.)

i. Set the nodes to par-

ticipate in the data
links.

Data link startup node
only

This manual is related to the following products: