beautypg.com

2-2 general specifications, General specifications – Omron CQM1H-CLK21 User Manual

Page 36

background image

13

Specifications and Configurations

Section 1-2

Converting Part of the Transmission Line to Optical Fiber

Two Repeater Units of the same model must be used when part of the trans-
mission line uses optical fiber.

Maximum Configuration of 62 Nodes

The following Controller Link Units/Support Boards must be used to construct
a network with more than 32 nodes:

CS1W-CLK21-V1
CJ1W-CLK21-V1
3G8F7-CLK21-E-V1

Note

1.

The network will not operate correctly unless all nodes within the network
use the above Units/Boards.

2.

Only node addresses 1 through 32 can be used on networks for which 62
nodes have not been enabled.

1-2-2

General Specifications

General specifications are the same for the C200HX/HG/HE, CS-series, CJ-
series, CVM1, CV-series, and CQM1H-series PLCs.

Wired Controller Link Unit

Wired Controller Link Unit

Twisted-pair cable

Twisted-pair cable

Optical cable (H-PCF or GI)

CS1W-RPT02 or
CS1W-RPT03
Repeater Units

Wired Controller Link Unit

Wired Controller Link Unit

Twisted-pair cable

32 nodes max.

Twisted-pair cable

32 nodes max.

CS1W-RPT01
Repeater Unit

This manual is related to the following products: