beautypg.com

Omron CQM1H-CLK21 User Manual

Page 339

background image

316

Error Log

Section 9-3

0101
Hex

Transmission failed; local node
not in Network

Command block
Bits 0 to 7:

Source node address

Bits 8 to 14:

Source Network
address

Bit 15:

OFF

Response block
Bits 0 to 7:

Destination node
address

Bits 8 to 14:

Destination Network
address

Bit 15:

ON

(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)

Refer to page 276
Troubleshooting
Using Indicators
and
place the local node
into Network.

No

All

0103
Hex

Transmission failed; retry count
exceeded

Using the Controller
Link Support Soft-
ware or FINS
commands, run
echoback test and
check operating envi-
ronment if errors
occur.

No

All

0104
Hex

Transmission failed; maximum
number of frames exceeded.

Reduce the number
of events per com-
munications cycle or
increase the maxi-
mum number of
network parameter
frames.

No

All

0105
Hex

Transmission failed; node
address incorrect

Refer to 4-2 CJ-
series Controller Link
Units
or
4-4 CVM1
and CV-series Con-
troller Link Units
an
d
check node address
settings to be sure
they are within range
and unique.

No

All

0106
Hex

Transmission failed; redundant
node address

Correct node
addresses so that
they are unique
within the same
Network.

No

All

0107
Hex

Transmission failed; destination
node not in Network

Refer to 9-1 Trouble-
shooting Using Indi-
cators
a
nd place
destination node into
Network.

No

All

0108
Hex

Transmission failed; specified
Unit does not exist

Refer to 4-4 CVM1
and CV-series Con-
troller Link Units
an
d
check unit address
and unit number of
destination.

No

All

Error

code

Contents

Detail code

Correction

Written to

EEPROM

Applicable

PLC

1st byte

2nd byte

This manual is related to the following products: