beautypg.com

Omron CQM1H-CLK21 User Manual

Page 38

background image

15

Specifications and Configurations

Section 1-2

Communications Specifications when Using the CS1W-RPT01 Repeater Unit in a Wired
Network

Note

1.

Specifications within a segment are identical to the specifications of a
Wired Controller Link Network.

2.

Maximum transmission distance: Total length of cables in the longest path
connecting any two nodes.

3.

A maximum of 62 nodes is possible only when using CS1W-CLK21-V1,
CJ1W-CLK21-V1 and 3G8F7-CLK21-V1 Units.

4.

Maximum number of Repeater stages: The maximum number of Repeater
Units that can be inserted into the path connecting any two nodes. For
wire-to-optical connection, two Repeater Units make up a single set, which
is counted as a single Repeater stage.

5.

The Repeater Units each have a unique node address. Up to 32 Units,
consisting of Controller Link Units and Repeater Units, can be connected
within a single segment.

Specifications of Optical Fiber Cables Used with Wire-to-Optical
Connections

Item

Within 1 segment (See

note 1.)

Entire network

Transmission path form

Multi-drop

Tree type (Connection of
segments with Repeaters)

Baud rate and maximum trans-
mission distance (See note 2.)

2 Mbps: 500 m
1 Mbps: 800 m
500 Kbps: 1 km

2 Mbps: 1.5 km
1 Mbps: 2.4 km
500 Kbps: 3.0 km

Maximum number of nodes

Total number of Control-
ler Link Units + Repeater
Units: 32 nodes (See
note 5.)

Controller Link Units/Sup-
port Boards (See note 3.):
62 nodes

Maximum number of Repeater
stages (See note 4.)

---

2 stages

Wire

Optical
fiber
cable

: Wire-to-wire Repeater Unit

: Range of a single segment

: Controller Link Unit/Support

Board

: Wire-to-optical Repeater Unit

(two Units used in a pair)

Note: The Repeater Unit will be

counted in the number of
nodes for each segment that
it is connected to.

Item

H-PCF type

GI type

Optical fiber cable

H-PCF 200/230

µ

m two-

core cable

GI 50/125

µ

m two-core cable

or GI 62.5/125

µ

m two-core

cable

Maximum transmission
distance (See note 2.)

Adhesion-polished: 1 km
Crimp cut: 800 m

50/125

µ

m: 1 km

62.5/125

µ

m: 2 km

This manual is related to the following products: