Sw1 - san unit number setting, E ‚b ‚p ‚t ‚o ‚o – FEC DSP1500 (SAN3) User Manual
Page 51

PAGE 4-19
enFORCE
Operation Manual
4.8 SW1 - Axis Unit Number Setting
In a multiple SAN Unit system, it is necessary to address each unit for communication purposes.
The number is set with the front DIP switch (4 thru 8) of the SAN Unit. If the display unit is installed,
it must be removed to access the DIP switches.
No two units can share the same number. However, units may be skipped or started from a number
besides one. Typically, units should be numbered sequentially (Ex: 1-31).
DIP Switch Number
Unit
Number
4 5 6 7 8
1
OFF OFF OFF OFF ON
2
OFF OFF OFF ON OFF
3
OFF OFF OFF ON ON
4
OFF OFF ON OFF OFF
5
OFF OFF ON OFF ON
6
OFF OFF ON ON OFF
7
OFF OFF ON ON ON
8
OFF ON OFF OFF OFF
9
OFF ON OFF OFF ON
10
OFF ON OFF ON OFF
11
OFF ON OFF ON ON
12
OFF ON ON OFF OFF
13
OFF ON ON OFF ON
14
OFF ON ON ON OFF
15
OFF ON ON ON ON
16
ON OFF OFF OFF OFF
17
ON OFF OFF OFF ON
18
ON OFF OFF ON OFF
19
ON OFF OFF ON ON
20
ON OFF ON OFF OFF
21
ON OFF ON OFF ON
22
ON OFF ON ON OFF
23
ON OFF ON ON ON
24
ON ON OFF OFF OFF
25
ON ON OFF OFF ON
26
ON ON OFF ON OFF
27
ON ON OFF ON ON
28
ON ON ON OFF OFF
29
ON ON ON OFF ON
30
ON ON ON ON OFF
31
ON ON ON ON ON
Special Settings (positions 1 - 3)
1 ON:
CAL/Zero acceptance window = +/-10% of full scale load.
OFF: CAL/Zero acceptance window = +/-4% of full scale load. (Default)
2 ON:
Parameter changes made by communicating are not saved on EEPROM.
OFF:
Parameter changes made by communicating are saved on EEPROM. (Default)
3 ON: Ramp Down Disabled
The slow down is done rapidly.
It is used to gain cycle time, etc., however, the burden on the gear will be greater.
OFF: Ramp Down Enabled
(Default)
The slow down is done slowly.
If not used, set DIP switches number 1 thru 3 in the OFF position.
SAN Unit must be powered off and on again for switch changes to take effect.
RUN
BYPASS
SW1
CON1
POWER
BUSY
SV.
ABN.
ACC.
REJ.
‚` ‚e ‚b ‚P ‚T ‚O ‚O
1
2
34
5
6
7
8
OFF‘¤
ON‘¤
DSP1500
Chapter 4: System Setup and Wiring