PAGE 4-15
enFORCE
Operation Manual
TIMING SIGNAL: [OUT DATA9] (Special Function)
This signal is active if Parameter 00, D-No. 0A (Option Output Signal) is set to a
number other than 0.
When activated, D-No. 30, 31, 32 and 33 of Parameters 1~32 (normally Rate 1 and
Rate 2 limits) will be used to set ON and OFF limits for the Timing Signal.
[30: Advance Direction ON Distance]
[31: Advance Direction OFF Distance]
[32: Return Direction ON Distance]
[33: Return Direction OFF Distance]
This may be useful when interfacing with other fixture processes or tooling (IE:
vacuum, clamps, etc.) or when other processes need to know when the press ram is
clear.
CYCLE OK: [OUT DATA10] (Special Function – Distance Control Methods)
This signal is active if Parameter 00, D-No. 0A (Option Output Signal) is set to a
number other than 0. When inactive this signal is the BANK 1 Input Echo signal.
This setting represents a distance (in millimeters) that the CYCLE OK signal will turn
on before reaching Standard Distance. The signal will turn off when Standard
Distance is reached. A setting of 1 to 9mm is possible.
Example: If Parameter 00, D-No. 0A is set to 6xxx. The CYCLE OK signal will
turn on 6mm before reaching Standard Distance.
Chapter 4: System Setup and Wiring
30
33
ON
OFF
31
OFF
ON
32
0mm
150mm
Standard Distance
ON
6 mm
Example #1
[30: 50.0mm]
[31: 120.0mm]
[32: 150.0mm]
[33: 100.0mm]
30
33
ON
OFF
150mm
Example #2
[30: 50.0mm]
[31: Max Distance]
[32: Max Distance]
[33: 100.0mm]
0mm