Data number 15, 23 & 16 – FEC DSP1500 (SAN3) User Manual
Page 102

PAGE 6-40
enFORCE
Operation Manual
¾
Data Number 15 [1
ST
Load]
¾
Data Number 23 [1
ST
Distance]
Ending point of calculation of 1
ST
Rate.
In a 2 step operation, ending of 1
ST
step.
A setting is possible from 0 to 105% of full-scale value.
These two settings may be used together to detect foreign substances (early load).
If the press reaches [15: 1
ST
Load] before exceeding [23: 1
ST
Distance], a “1
ST
Rate Low”
reject will occur and press operation will stop.
¾
Data Number 16 - SNUG Load
The starting point of calculation of [22: Standard Distance]. If set to 0, distance is
calculated from start.
A setting is possible from 0 to 105% full-scale value.
For example, if [16: SNUG Load] is set to 1KN and [22: Standard Distance] is 10mm:
The distance data that is effected by [16: SNUG Load] is [22: Standard
Distance] and [24: Crossover Distance]. All other distance data uses the
[62: Return Position] value.
Chapter 6: System Operation
Load
Distance
SNUG
1
KN
10
mm
Judge Load
1
ST
Judgment Zone
[1
ST
Rate Low]
Load
Distance
[15] 1
st
Load
[23] 1
st
Distance
[1
ST
Judgment]