San unit design & mounting dimensions – FEC DSP1500 (SAN3) User Manual
Page 35

PAGE 4-3
enFORCE
Operation Manual
4.2 SAN Unit Design and Mounting Dimensions
SAN units must be mounted with a minimum clearance of 12mm on each side to allow proper heat
dissipation. Cable connections on the front of the units require 100mm of clearance.
Allow a minimum of 100mm clearance on the bottom of each controller for cable hook up when
updating firmware.
SAN units must be located a minimum of 600mm from any high transient voltage power source.
Mounting: Top
(1) place
#8-32 screw
Bottom (2) places
#8-32 screw
Weight: SAN3-24S – 1.4 kg
SAN3-40S – 1.8 kg
The diagram shown above shows the dimensions of the SAN3-40S.
The protrusion of the heat sink plate (14mm) is on the SAN3-40S only, therefore the width of the
SAN3-24S is 60mm as opposed to 74mm.
SAN3-24S, SAN3-40S
Chapter 4: System Setup and Wiring
- AFC1500 (4 pages)
- AFC1500 (14 pages)
- AFC1500 (20 pages)
- AFC1500 (2 pages)
- AFC1500 (63 pages)
- AFC1500 (83 pages)
- AFC1500 (129 pages)
- AFC1500 (198 pages)
- AFC1200 (6 pages)
- AFC1200 (8 pages)
- AFC1200 (12 pages)
- AFC1200 (5 pages)
- AFC1200 (22 pages)
- AFC1200 (34 pages)
- AFC1200 (16 pages)
- AFC1200 (9 pages)
- AFC1200 (13 pages)
- AFC1200 (4 pages)
- AFC1200 (23 pages)
- AFC1200 (42 pages)
- AFC1200 (10 pages)
- AFC1200 (33 pages)
- AFC1200 (14 pages)
- AFC1200 (24 pages)
- AFC1200 (93 pages)
- AFC1200 (30 pages)
- AFC1200 (90 pages)
- AFC1150 (4 pages)
- AFC1150 (10 pages)
- AFC1150 (18 pages)
- AFC1150 (6 pages)
- AFC1100 (7 pages)
- AFC1100 (9 pages)
- AFC1100 (4 pages)
- AFC1100 (13 pages)
- AFC1100 (21 pages)
- AFC1100 (8 pages)
- AFC1100 (28 pages)
- AFC1100 (18 pages)
- MICRO NR (118 pages)
- FUSIONE-HS-2 (183 pages)
- DSP1500 (SAN3) (6 pages)
- DSP1500 (SAN3) (10 pages)
- DSP1500 (SAN3) (8 pages)
- DSP1500 (SAN3) (26 pages)