12 options group – Honeywell UDC2500 User Manual

Page 81

background image

Configuration

4/07

UDC2500 Universal Digital Controller Product Manual

67

3.12 Options Group

Introduction

The Options group lets you configure the remote mode switch (Digital Inputs) to a
specific contact closure response, or configure the Auxiliary Output to be a specific
selection with desired scaling.

Function Prompts

Table 3-13 OPTION Group (Numeric Code 900) Function Prompts

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

AUXOUT 901

AUXILIARY OUTPUT SELECTION

This selection provides an mA output
representing one of several control
parameters. The display for auxiliary output
viewing will be in engineering units for all but
output. Output will be displayed in percent.

ATTENTION Other prompts affected by
these selections: 4mA VAL and 20mA VAL.

ATTENTION Output cannot be configured
when Three Position Step Control is used.

DIS

0

NO AUXILIARY OUTPUT

IN1

1

INPUT 1—This represents the configured
range of input 1.

FOR EXAMPLE:
Type J Thermocouple (0 °F to 1600 °F)
0 °F display = 0 % output
1600 °F display = 100 % output

IN2

2

INPUT 2 represents the value of the
configured range of input 2.

PROC

3

PROCESS VARIABLE—Represents the
value of the Process Variable. PV = Input
XxRatioX + BiasX