3 accutune – Honeywell UDC2500 User Manual
Page 215
Modbus Read, Write and Override Parameters plus Exception Codes
4/07
UDC2500 Universal Digital Controller Product Manual
201
10.7.3 Accutune
Table 10-11 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Accutune.
Table 10-11 Set-up Group – Accutune
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Fuzzy Overshoot
Suppression
00C1
193
INT
R/W
0 = Disabled
1 = Enabled
Accutune Enable
0098
152
INT
R/W
0 = Accutune Disabled
1 = Tune
Accutune Duplex
selection
E1 225 INT
R/W 0 = Manual
1 = Auto
2 = Disable (blend)
Accutune Error
(Read only)
0097 151
INT R/W
0 = None
3 = Process Identification
failed
4 = Accutune aborted on
command
5 = Running