7 input 2 calibration procedure – Honeywell UDC2500 User Manual

Page 161

background image

Input Calibration

4/07

UDC2500 Universal Digital Controller Product Manual

147

0 to 2 Volts, 0 to 5 Volts, or 1 to 5 Volt Inputs – Input 2

Refer to Figure 5-9 and wire the controller according to the procedure given in Table
5-12.

Table 5-12 Set Up Wiring Procedure for 0 to 2 Volts, 0 to 5 Volts, or 1 to 5

Volts – Input 2

Step

Action

1

Connect the copper leads from the calibrator to the Input #2 terminals as shown in
Figure 5-8.

2

Place voltage source at zero before switching on.

3

Do not switch voltage source ON/OFF while connected to the instrument.

Voltage
Source

26 +
27 -

Copper Leads
Equal Length

+
_

25 (no connection)

Voltage
Source

26 +
27 -

Copper Leads
Equal Length

+
_

25 (no connection)

Figure 5-9 Wiring Connections for 0 to 2 Volts, 0 to 5 Volts or 1 to 5 Volts

Input – Input 2

5.7 Input 2 Calibration Procedure

Preliminary Steps

• Apply power and allow the controller to warm up for 30 minutes before you calibrate.
• Please read Subsection 5.6 – before beginning the procedure.
Make sure you have LOCK set to NONE. See Subsection 3.4 - Tuning Set Up

Group.

Continued next page