beautypg.com

Honeywell UDC2500 User Manual

Page 211

background image

Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

197

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Lockout
(keyboard only)

Changes to data are
always possible via
communications
regardless of this
configuration.

0084 132

INT R/W

0 = No Lockout
1 = Calibration Locked out
2 = +Configuration – Timer,

Tuning, SP Ramp,
Accutune are read/write

3 = +View – Tuning and SP

Ramp are read/write, no
other parameters are
available

4 = Maximum Lockout

Security Code

0050

080

INT

R/W

0 to 9999

Man/Auto Key
Lockout

00BF 191

INT

R/W

0 = Disable
1 =Enable

Run/Hold Key
Lockout

00EE 238

INT

R/W

0 = Disable
1 =Enable

Setpoint Key
Lockout

00ED 237

INT

R/W

0 = Disable
1 =Enable

NOTE 1: Writes to these locations are not available when Accutune is enabled.