4 algorithm – Honeywell UDC2500 User Manual
Page 216
Modbus Read, Write and Override Parameters plus Exception Codes
202
UDC2500 Universal Digital Controller Product Manual
4/07
10.7.4 Algorithm
Table 10-12 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Algorithm.
Table 10-12 Set-up Group – Algorithm
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Control
Algorithm
Selection
(Selection here will
affect ID code 160 in
Output Algorithms.)
0080 128
INT R/W
0 = ON/OFF
1 = PID-A
2 = PID-B
3 = PD-A with Manual
Reset
4 = Three Position Step
5 = Disable
Timer
00D8
216
INT
R/W
0 = Disable
1 = Enable
Period
0063
099
FP
R/W
00.00 TO 99.59
Start (Initiation)
00D9
217
INT
R/W
0 = Key (Run/Hold Key)
1 = Alarm 2
LDISP (Selection) 00DA 218
INT
R/W
0 = TI REM
1 = Elapsed Time
Timer Reset
00D6
214
INT
R/W
0 = Key (Run/Hold Key)
1 = AL1 (Alarm 1 or Key)
Timer Increment
00D7
215
INT
R/W
0 = Min (Counts hr/min)
1 = Sec (Counts min/sec)