beautypg.com

4 algorithm – Honeywell UDC2500 User Manual

Page 216

background image

Modbus Read, Write and Override Parameters plus Exception Codes

202

UDC2500 Universal Digital Controller Product Manual

4/07

10.7.4 Algorithm

Table 10-12 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Algorithm.

Table 10-12 Set-up Group – Algorithm

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Control

Algorithm

Selection

(Selection here will
affect ID code 160 in
Output Algorithms.)

0080 128

INT R/W

0 = ON/OFF
1 = PID-A
2 = PID-B
3 = PD-A with Manual

Reset

4 = Three Position Step
5 = Disable

Timer

00D8

216

INT

R/W

0 = Disable

1 = Enable

Period

0063

099

FP

R/W

00.00 TO 99.59

Start (Initiation)

00D9

217

INT

R/W

0 = Key (Run/Hold Key)

1 = Alarm 2

LDISP (Selection) 00DA 218

INT

R/W

0 = TI REM

1 = Elapsed Time

Timer Reset

00D6

214

INT

R/W

0 = Key (Run/Hold Key)

1 = AL1 (Alarm 1 or Key)

Timer Increment

00D7

215

INT

R/W

0 = Min (Counts hr/min)

1 = Sec (Counts min/sec)