Modbus Read, Write and Override Parameters plus Exception Codes
4/07
UDC2500 Universal Digital Controller Product Manual
199
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Controller Status
at Program End
00B4
180
INT
R/W
0 = Last Setpoint and Mode
1 = Manual, Failsafe Output
Reset SP Program
(ToBEGIN)
00B3
179
INT
R/W
0 = Disable
1 = Via Keypad
PV Hotstart
00E2
226
INT
R/W
0 = Disabled
1 = Enabled
Segment #1 Ramp
Time
0039
057
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #2 Soak
Setpoint Value
003A
058
FP
R/W
Within Setpoint Limits
Segment #2 Soak
Time
003B
059
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #3 Ramp
Time
003C
060
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #4 Soak
Setpoint Value
003D
061
FP
R/W
Within Setpoint Limits
Segment #4 Soak
Time
003E
062
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #5 Ramp
Time
003F
063
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #6 Soak
Setpoint Value
0040
064
FP
R/W
Within Setpoint Limits
Segment #6 Soak
Time
0041
065
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #7 Ramp
Time
0042
066
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #8 Soak
Setpoint Value
0043
067
FP
R/W
Within Setpoint Limits