beautypg.com

1 tune for simplex outputs, 2 tune for duplex (heat/cool) – Honeywell UDC2500 User Manual

Page 119

background image

Monitoring and Operating the Controller

4/07

UDC2500 Universal Digital Controller Product Manual

105

At the end of the tuning process, the controller immediately calculates the tuning
constants and enters them into the Tuning group, and begins PID control with the correct
tuning parameters. This works with any process, including integrating type processes,
and allows retuning at a fixed setpoint.

4.11.1

Tune for Simplex Outputs

After “TUNE” has been enabled, you can start Accutune as shown in Table 4-11.

Table 4-11 Procedure for Starting “TUNE”

Step

Operation

Press

Result

1

Configure LSP1

Lower

Display

Lower

Display

Lower

Display

Until SP (Local Setpoint 1) shows
in the lower display.

2

or

Until LSP1 is to the desired value.

3

Switch to
“Automatic” Mode

M-A

Reset

M-A

Reset

M-A

Reset

Until the “A” indicator is lighted (on
controllers with Manual option).

4

Show Tuning
Prompt

Lower

Display

Lower

Display

Lower

Display

Until “NoTUNE” is shown on lower
display.

5

Initiate Tuning

Select “DoSLOW” or “DoFAST” in
lower display.

6

Tuning in operation

Lower

Display

Lower

Display

Lower

Display

Upper display will flash “TUNE” as
long as ACCUTUNE process is
operating. When process
completes, tuning parameters are
calculated and lower display will
show “NoTune” prompt.

ATTENTION

The Accutune process may be aborted at any time by changing the lower display back to “NoTUNE” or
by switching the controller into Manual Mode.

4.11.2

Tune for Duplex (Heat/Cool)

Accutune for applications using Duplex (Heat/Cool) control.

The controller must be configured to have two local setpoints unless Blended Tuning is
desired (see below). See Subsection 3.11- Control Set Up Group for details on
configuring two local setpoints. During tuning, the Accutune III process assumes that
Local Setpoint 1 will cause a Heating demand (output above 50%), and the tuning
parameters calculated for that setpoint are automatically entered as PID SET 1. Likewise,
Accutune III assumes that Local Setpoint 2 will cause a Cooling demand (output less
than 50%), and the tuning parameters calculated for that setpoint are automatically
entered as PID SET 2.