Table 2-6 Universal Output Functionality and Restrictions

Function of Other Outputs

Output Algorithm

Type

Output 1/2

Option

Function of

Output 1/2

Output #3

Output #4

Auxiliary Output

Single Relay

Output 1

Alarm 2

Alarm 1

Not Needed

Current Output

INU

Output 1

Alarm 1

Not Needed

Time Simplex

Dual Relay

Output 1

Alarm 2

Alarm 1

Not Needed

Single Relay

Output 1

Output 2

Alarm 1

Not Needed

Current Output

INU

Output 2

Output 1

Not Needed

Time Duplex or
TPSC

Dual Relay

Outputs 1 and

2

Alarm 2

Alarm 1

Not Needed

Single Relay

INU

Alarm 2

Alarm 1

Output 1

Current Output

Output 1

Alarm 2

Alarm 1

Not Needed

Current Simplex

Dual Relay

INU

Alarm 2

Alarm 1

Output 1

Single Relay

INU

Alarm 2

Alarm 1

Outputs 1 and 2

Current Output

Outputs 1 and

2

Alarm 2

Alarm 1

Not Needed

Current Dup. 100%
Current = COOL
and HEAT

Dual Relay

INU

Alarm 2

Alarm 1

Outputs 1 and 2

Single Relay

N/A

N/A

N/A

N/A

Current Output

Output 1

Alarm 2

Alarm 1

Output 2

Current Duplex
50%
Current = HEAT
Aux Out = COOL

Dual Relay

N/A

N/A

N/A

N/A

Single Relay *

Output 1

Output 2

Alarm 1

Output 2

Current Output

Output 2

Output 2

Alarm 1

Not Needed

Current/Time
Current = COOL
Time = HEAT

Dual Relay *

Outputs 1 & 2

Alarm 2

Alarm 1

Output 2

Single Relay *

Output 1

Output 2

Alarm 1

Output 1

Current Output

Output 1

Output 2

Alarm 1

Not Needed

Time/Current
Time = COOL
Current = HEAT

Dual Relay *

Outputs 1 & 2

Alarm 2

Alarm 1

Output 1

TPSC = Three Position Step Control

N/A = Not Available – This output algorithm type cannot be performed with this Output 1/2

option.

INU = Installed, Not Used – The installed Output 1/2 option is not used for the configured

output algorithm type.

Not Needed = Auxiliary Output is Not Needed to provide the desired output algorithm and can

be used for another purpose. With the proper configuration, Auxiliary Output
could also be used as a substitute for the Current Output

* To obtain this output algorithm type with these Output 1/2 Options: 1) Configure the

OUTALG selection as “TIME D”; 2) Configure Auxiliary Output for “OUTPUT” and; 3)
Scale the Auxiliary Output as necessary for the desired output algorithm type. For these