Modbus Read, Write and Override Parameters plus Exception Codes
200
UDC2500 Universal Digital Controller Product Manual
4/07
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Segment #8 Soak
Time
0044
068
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #9 Ramp
Time
0045
069
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #10
Soak Setpoint
Value
0046
070
FP
R/W
Within Setpoint Limits
Segment #10
Soak Time
0047
071
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Segment #11
Ramp Time
0048
072
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #12
Soak Setpoint
Value
0049
073
FP
R/W
Within Setpoint Limits
Segment #12
Soak Time
004A
074
FP
R/W
99.59 (0-99 Hrs:0-59 Min)