Installation

4/07

UDC2500 Universal Digital Controller Product Manual

27

Alarm
Relay#1

Out Relay#1

L1

L2/N

4

5

7

8

9

N.O.

N.C.

N.O.

Cool Relay Load

Load

Supply
Power

Time Duplex with a Dual Relay Board

1

1

Dual Electromechanical relays are rated at 2 Amps @120 Vac or 240 Vac or 30 Vdc. Customer should size
fuses accordingly. Use Fast Blo fuses only.

N.O.

19

20

21

22

23

24

25

26

27

To terminal

4 or 6

Alarm
Relay#2

N.C.

N.O.

6

Relay Load

To terminal

7 or 9

Relay Load

2

2

Load

Supply
Power

Load

Supply
Power

Heat Relay Load

Out Relay#2

2

Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc.
Customer should size fuses accordingly. Use Fast Blo fuses only.

Figure 2-11 Dual Electromechanical Relay Option Output

See Table 2-6 for relay terminal connections for other Output Algorithm Types.

Alarm
Relay#1

L1

L2/N

4

5

7

8

9

N.C.

N.O.

2

When the instrument has the Current Output as shown, no Alarms are available when using the Time Proportional Duplex or
Three Position Step Control Output Algorithms, as these outputs require both available relays.

Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc.
Customer should size fuses accordingly. Use Fast Blo fuses only.

19

20

21

22

23

24

25

26

27

6

To terminal

7 or 9

Relay Load

2

Load

Supply
Power

+

Controller Load

0-1000 ohms

Current Output

4–20 mA

1

1

To terminal

4 or 6

Alarm
Relay#2

N.C.

N.O.

Relay Load

2

Load

Supply
Power

Figure 2-12 Current Output

See Table 2-6 for relay terminal connections for other Output Algorithm Types.