beautypg.com

Honeywell UDC2500 User Manual

Page 224

background image

Modbus Read, Write and Override Parameters plus Exception Codes

210

UDC2500 Universal Digital Controller Product Manual

4/07

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

High Output
Limit

000E

014

FP

R/W

–5 to 105% of output

Low Output
Limit

000F

015

FP

R/W

–5 to 105% of output

Output Deadband
for Time Duplex

0012

018

FP

R/W

–5 to +25.0%

Output Deadband
for TPSC

0014

020

FP

R/W

0.5 to 5.0%

Output
Hysteresis

0013

019

FP

R/W

0.0 to 100.0% of PV

Failsafe Mode

00D5

213

INT

R/W

0 = Latching
1 = Non latching

Failsafe Output
Level

0028

040

FP

R/W

0 to 100%

TPSC Power-up
Output

00B7

183

INT

R/W

0 = Last
1 = Failsafe

TPSC Failsafe
Output

00B8

184

INT

R/W

0 = Motor goes to closed

position (0%)

1 = Motor goes to open

position (100%)

Proportional
Band Units

0094

148

INT

R/W

0 = Gain
1 = Proportional band

Reset Units

0095

149

INT

R/W

0 = Minutes
1 = RPM

PV High Range

0036

054

FP

R

PV High Limit

PV Low Range

0037

055

FP

R

PV Low Limit