Honeywell UDC2500 User Manual
Page 224
Modbus Read, Write and Override Parameters plus Exception Codes
210
UDC2500 Universal Digital Controller Product Manual
4/07
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
High Output
Limit
000E
014
FP
R/W
–5 to 105% of output
Low Output
Limit
000F
015
FP
R/W
–5 to 105% of output
Output Deadband
for Time Duplex
0012
018
FP
R/W
–5 to +25.0%
Output Deadband
for TPSC
0014
020
FP
R/W
0.5 to 5.0%
Output
Hysteresis
0013
019
FP
R/W
0.0 to 100.0% of PV
Failsafe Mode
00D5
213
INT
R/W
0 = Latching
1 = Non latching
Failsafe Output
Level
0028
040
FP
R/W
0 to 100%
TPSC Power-up
Output
00B7
183
INT
R/W
0 = Last
1 = Failsafe
TPSC Failsafe
Output
00B8
184
INT
R/W
0 = Motor goes to closed
position (0%)
1 = Motor goes to open
position (100%)
Proportional
Band Units
0094
148
INT
R/W
0 = Gain
1 = Proportional band
Reset Units
0095
149
INT
R/W
0 = Minutes
1 = RPM
PV High Range
0036
054
FP
R
PV High Limit
PV Low Range
0037
055
FP
R
PV Low Limit