Input Calibration

4/07

UDC2500 Universal Digital Controller Product Manual

139

Table 5-2 Voltage and Milliamp Equivalents for Input 2 Range Values

Range Values

Sensor Type

PV Input Range

0 %

100 %

Linear

Milliamps

4 to 20 mA
0 to 20 mA

4.00 mA
0.00 mA

20.00 mA
20.00 mA

Volts

1 to 5 Volts
0 to 5 Volts
0 to 2 Volts

1.00 Volts
0.00 Volts
0.00 Volts

5.00 Volts
5.00 Volts
2.00 Volts

5.3 Preliminary Information

Disconnect the Field Wiring

Tag and disconnect any field wiring connected to the input (#1 or #2) terminals on the
rear of the controller.

XXXX

R

+

_

Input 1

Connections

25 R
26 +
27 –

mA+

Volt+

Input 2

Connections

22 mA+
23 V+
24 –

_

Input 1

Input 2

Figure 5-1 Input 1 and Input 2 Wiring Terminals

Equipment Needed

Table 5-3 lists the equipment you will need to calibrate the specific types of inputs that
are listed in the table. You will need a screwdriver to connect these devices to your
controller.

Table 5-3 Equipment Needed

Type of Input

Equipment Needed

Thermocouple
Inputs (Ice Bath)

• A calibrating device with at least ± 0.02 % accuracy for use as a

signal source such as a millivolt source.

• Thermocouple extension wire that corresponds with the type of

thermocouple that will be used with the controller input.

• Two insulated copper leads for connecting the thermocouple

extension wire from the ice baths to the mV source.

• Two containers of crushed ice.

Thermocouple
Inputs (T/C Source)

• A calibrating device with at least ± 0.02 % accuracy for use as a

signal source such as a millivolt source.

• Thermocouple extension wire that corresponds with the type of

thermocouple that will be used with controller input.