Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

213

10.7.10 Communications

Table 10-18 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Communications.

Table 10-18 Set-up Group – Communications

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Communication
Address

004D

77

FP

R/W

1 - 99

Communications
Type

00E7 231

INT R/W

0 = None
1 = Disable
2 = RS-485 Modbus
3 = Ethernet

IR Port Enable

00F1

241

INT

R/W

0 = Disable
1 =- Enable

Baud Rate

00E8

232

INT

R/W

0 = 4800
1 = 9600
2 = 19200
3 = 38400

Transmit Delay

004E

78

FP

R/W

Response Delay in ms
(1 to 500) +6ms

Floating Point
Byte Order

00E9

233

INT

R/W

0 = Big Endian
1 = Big Endian Byte Swap
2 = Little Endian
3 = Little Endian Byte Swap

Shed Enable

00EA

234

INT

R/W

0 = Enable
1 = Disable

Shed Time

004F

79

INT

R/W

0 = No Shed
1 = 255 sample periods

Shed Mode and
Output

00A2 162

INT R/W

0 = Last Mode and Last Output
1 = Manual Mode, Last Output
2 = Manual Mode, Failsafe Output
3 = Automatic Mode

Shed Setpoint
Recall

00A3

163

INT

R/W

0 = To Last Local Setpoint used
1 = CSP

Computer
Setpoint Ratio

005A 90

FP R/W

–20.00 to 20.00

Computer
Setpoint Bias

005B 91

FP R/W

–999 to 9999.

Comm Data
Units

00A1 161

INT R/W

0 = Percent
1 = Engineering Units