Table 27 parallel system current table, Table 26, Table 27 – Emerson Liebert NX 480V User Manual

Page 97: Parallel system current table

background image

Specifications and Technical Data

89

Liebert NX, then add the appropriate length from the table and adequate slack for repair and mainte-

nance.

Table 26

Distance to connection points on the Liebert NX UPS

Connection Point on UPS

Distance

From Floor

in. (mm)

From Top of Unit

in. (mm)

Bypass AC input supply

13 (330)

66 (1676)

UPS output AC

13 (330)

66 (1676)

Battery power

13 (330)

66 (1676)

Auxiliary cables: Monitor board (U2)

67 (1702)

11 (279)

Liebert IntelliSlot Communications

60 (1524)

19 (483)

Ground

13 (330)

66 (1676)

Parallel Board

70 (1780)

11 (279)

Table 27

Parallel system current table

System

Size

Type

kVA

System I/P

Voltage

(VAC)

System Max

Input Current

System

Input OCPCB

Size (A)

O/P Voltage

(VAC)

Nominal

O/PCurrent

Rating (A)

Output

OCPCB

Size (A)

1+1

E

80

480V

202.5

300

480V

144.3

200

120

480V

135.0

200

480V

96.2

125

E1

80

480V

202.5

300

480V

144.3

200

120

480V

135.0

200

480V

96.2

125

E2

80

N/A

N/A

N/A

480V

144.3

200

120

N/A

N/A

N/A

480V

96.2

125

2+1

E

80

480V

405.0

600

480V

288.7

400

120

480V

270.0

350

480V

192.5

250

E1

80

480V

405.0

600

480V

288.7

400

120

480V

270.0

350

480V

192.5

250

E2

80

N/A

N/A

N/A

480V

288.7

400

120

N/A

N/A

N/A

480V

192.5

250

3+1

E

80

480V

607.5

800

480V

433.0

600

120

480V

405.0

600

480V

288.7

400

E1

80

480V

607.5

800

480V

433.0

600

120

480V

405.0

600

480V

288.7

400

E2

80

N/A

N/A

N/A

480V

433.0

600

120

N/A

N/A

N/A

480V

288.7

400

Use wiring rated at 75°C or greater.