10.1.4 Communication and Monitoring

Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card

This network interface card provides all real-time data and status information as SNMPv1 traps for

connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status

information and all measured parameters for display through a Web browser.
Table 21

Liebert NX communication options

Physical

description

of port

Labeled

ID Name

of Port

On the UPS

LCD screen,

under Settings,

controlled by:

Monitoring

Devices

supported

Baud

rate

Comments

Top

Liebert

IntelliSlot

Intellislot 2

(On Monitor

Board)

Comm 1

Multiport 4

any

Relaycard-int

any

Liebert IntelliSlot

WEB-LB

2400

Not simultaneous with

Multilink in RS232-1;

See 10.1.5 - Configuring

Baud Rates

Modbus/Jbus

2400

See 10.1.5 - Configuring

Baud Rates

Middle

Liebert

IntelliSlot

Intellislot 1

(On Monitor

Board)

Comm 2

Multiport 4

any

Relaycard-int

any

Liebert IntelliSlot

WEB-LB

2400

See 10.1.5 - Configuring

Baud Rates

Not simultaneous with

Multilink in RS232-2

Modbus/Jbus

2400

See 10.1.5 - Configuring

Baud Rates

Bottom

Liebert

IntelliSlot

Intellislot 3

(On Monitor

Board)

Comm 3

Multiport 4

any

Relaycard-int

any

Liebert IntelliSlot

WEB-LB

2400

See 10.1.5 - Configuring

Baud Rates

Modbus/Jbus

2400

See 10.1.5 - Configuring

Baud Rates

Top

DB9 port

RS232-1

Comm 1

MultiLink Serial

9600

Not simultaneous with Web

card in top Liebert

IntelliSlot.

Bottom

DB9 port

RS232-2

Comm 2

Service Software

(Reserved)

9600

Not simultaneous with Web

card in middle Liebert

IntelliSlot.