Operator Control and Display Panel

66

8.11 UPS Status Messages

The Liebert NX displays status changes as they occur in the current status window of the LCD,

then stores that data in the history log, as shown in Figure 48.

Current Status Window: The status messages are displayed chronologically and include the

date and time of the events. Three status messages are visible in the window at a time. To see

other messages, use the navigation keys to scroll up or down the list. A status message remains in

the current status area of the LCD until the status changes, when it is moved to the history log.

History Log: When a record moves to the history log, the time the status changed is recorded.

The history log can hold up to 512 records. History log records may be viewed by accessing the

Records menu.

Figure 48 Current status and history log records

See Appendix A for a complete list of status messages, along with a description and any recom-

mended actions.

?

Language

Battery

History

Inverter in setting

2003-01-21 12 :21:12
2003-01-21 12 :21:12

UPS shutdown

2003-01-21 12 :21:12
2003-01-22 12 :30:16

Bypass abnormal

2003-01-21 12 :21:12
2003-01-21 12 :30:16

F2

F4

HELP

F1

F3

Liebert NX

2007-01-12

12:30:36

80KVA-3X3

Single

Normal

Input disconnect closed

01-12 12:30

Output disconnect closed

01-12 12:30

Bypass disconnect open

01-12 12:30

History Log

(records

menu)

Current

Status

Messages