Electrical Connections

15

Frequency Converter Mode

If a frequency converter configuration is used, connect the AC input supply cables to the rectifier

input busbars (A-B-C terminals). Torque to 88 lb-in (10N-m) for M8 bolts. Ensure correct phase rota-

tion. There will not be any AC bypass supply cables to the bypass input (A-B-C terminals) and tighten

the connections.

2.2

Control Cables

2.2.1 Monitor Board Features

Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery

system (external battery circuit breaker, battery temperature sensor), communicate with a personal

computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).

The monitor board, arranged for this purpose, is located on the rear of the operator access door. The

main features are:

• Input and Output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
• Liebert IntelliSlot

®

interface

• Modem interface
• Temperature detect interface

Figure 5 shows the relationship and connection between the monitoring (U2) board and other boards

in the UPS.

Figure 5

Monitor board U2

NOTE
The operations described in this section must be performed by authorized electricians or

qualified technical personnel. If any difficulties arise, contact Liebert at 1-800-LIEBERT.

NOTE
For frequency converter operation, ensure that the linking busbars between the bypass and the

rectifier input are removed.

X1

User Interface

Board

U1

DSP Control

K1

Key & LED Board

U2

Monitor Board

M3

Parallel Logic

Board

M5

Auxiliary Power