beautypg.com

0 options, 1 communication and other user terminals, 1 analog input interface – Emerson Liebert NX 480V User Manual

Page 89: 2 power output, 3 liebert intellislot communication, Ptions, Communication and other user terminals

background image

Options

81

10.0 O

PTIONS

Several items of optional equipment are available for connection to the Liebert NX UPS.

10.1 Communication and Other User Terminals

The UPS can be integrated into advanced networking environments via UPS monitoring software

such as Windows-based UPS Monitor, MultiLink

, Nform

, SiteNet, Modbus / Jbus, SiteScan,

SiteScan 2, SNMP, etc. They allow UPS status monitoring and automatic and safe shutdown of the

server and PCs.

Figure 55 Monitoring board (U2) auxiliary terminal block detail

10.1.1 Analog Input Interface

At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is

2 percent. “ENV-T” is used for environment temperature detecting.

• X6 pin 1: Not used
• X6 pin 2: +12V
• X6 pin 3: ENV-T – environment temperature detection
• X6 pin 4: GND

10.1.2 Power Output

The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to

12V. The maximum current is 500mA.

10.1.3 Liebert IntelliSlot Communication

The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional communica-

tion cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary ESP2 protocol to cards that

translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide

dry contact signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is

operating.

NOTE: The black square ()

on each slot indicates Pin 1.

J3

J1

J13 J21 J25

J28

J4

J26 J30 J10

J22

J23

J12

J9

J15

J17

J24

X4

X4

J16

X1

X2

X3

Liebert IntelliSlot 2

Liebert IntelliSlot 1

Liebert IntelliSlot 3

J8

J2

LCD

BFP INV ACF

EPO

Dry in

MBC

BCB

X5

X6

X7

PWR

MODEM

SNMP CARD