background image

Battery Installation

25

3.6

Alber Monitoring System—Optional

The Liebert matching battery cabinet allows installing an optional Alber Battery monitoring system

in the cabinet. The Alber Battery Monitoring by Liebert continuously checks all critical battery

parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic

tests of internal resistance of each battery will verify the battery’s operating integrity. Additional

capabilities include automatic internal DC resistance tests and trend analysis providing the ability to

analyze performance and aid in troubleshooting.
The Alber monitoring system is installed inside the battery cabinet (see Figure 11). The monitoring

system requires approximately 0.5A, single-phase 480V.

This power can come from the output terminals of the UPS, a distribution panel, or another

UPS-protected source. This power is to be field supplied. See Figure 26 for wiring location.
For details about operating the Alber system, see the Alber Monitoring System manual.

NOTE
This power must be UPS protected.