Maintenance Mode

For maintenance or repair, the Liebert NX may be operated in maintenance mode. To place the Lie-

bert NX in maintenance mode, the load must be transferred to bypass and the inverter must be

turned off. When those conditions are met, the CB3 may be turned on and the UPS may be shut down,

permitting disconnecting the batteries for maintenance.

Parallel Redundancy Mode (System Expansion)

For higher capacity, higher reliability or both, the outputs of up to four UPS modules can be pro-

grammed for directly paralleling while a built-in parallel controller in each UPS ensures automatic

load-sharing.

Frequency Converter Mode

The Liebert NX can be programmed into frequency converter mode for either 50Hz or 60Hz stable

output frequency. The input frequency may vary from 57Hz to 66Hz. In this mode, the static bypass

operation is disabled and the battery becomes optional, depending on any requirement to operate in

battery mode (stored energy mode).

!

CAUTION

The internal maintenance bypass must not be used when the UPS system is in a parallel

system.

!

WARNING

The UPS input and output must be protected with external overcurrent protection devices. In

maintenance mode, the input and output busbars remain energized.