Relay card, Table 22 relay card pin configuration, Table 23 relay card jumper configuration – Emerson Liebert NX 480V User Manual

Page 93: Table 22, Relay card pin configuration, Table 23, Relay card jumper configuration

background image

Options

85

Relay Card

The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig-

nals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other

relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A and supported in any of the three Liebert IntelliSlot bays

on the Liebert NX.
Table 22

Relay Card pin configuration

Pin

Function

Operation

1

UPS Fault

Closed if no UPS failure

2-3

Not Used

4

UPS Fault

Closed if UPS fails

5

Summary Alarm**

Closed if SUMMARY ALARM** occurs

6

Summary Alarm**

Closed if no alarm conditions are present

7

Any Mode Shutdown return

Not supported – use External EPO terminal

8

Not Used

9

Common - Low Battery

10

Low Battery

Closed if battery is OK

11

Low Battery

Closed if LOW BATTERY point occurs

12-13

Not Used

14

UPS Any Mode Shutdown

Not supported – use External EPO terminal

15

On UPS

Closed if ON UPS (inverter) power

16

On Battery

Closed if ON BATTERY power (Utility failure)

17

Common - UPS Fault, Summary Alarm,

On UPS, On Battery, On Bypass

18

On Battery

Closed if not ON Battery power (Utility OK)

19-23

Not Used

24

On Bypass

Closed if ON BYPASS

25

Not Used

**A Summary Alarm occurs when any of the following conditions exist:
1. Utility power is out of the acceptable range (voltage and/or frequency).
2. UPS is in BYPASS MODE (load not on Inverter power).
3. UPS Battery is LOW.
4. UPS fault has occurred.

Table 23

Relay card jumper configuration

Number

Connection

Description

JP01

Pin 9 to Pin 17

Allows all relay COMMONS to be tied together.

ANY JP02

Pin 7 to Pin 17

REMOVE - (Interconnects all relay COMMONS and the (not

supported) MODE SHUTDOWN Return