beautypg.com

4 battery run times, Table 35 estimated battery run time, minutes, Battery run times – Emerson Liebert NX 480V User Manual

Page 100: Table 35, Estimated battery run time, minutes

background image

Specifications and Technical Data

92

11.4 Battery Run Times

Table 35

Estimated battery run time, minutes

UPS Rating/Model

Number of Cabinets

1

2

3

4

40kVA UPS

UPS12-100MR

5

18

32

47

UPS12-150MR

13

33

53

75

UPS12-210MR

21

51

81

123

60kVA UPS

UPS12-100MR

-

9

18

27

UPS12-150MR

7

19

33

47

UPS12-210MR

11

31

51

73

80kVA UPS

UPS12-100MR

-

5

11

18

UPS12-150MR

-

13

22

33

UPS12-210MR

6

21

36

51

100kVA UPS

UPS12-100MR

-

-

8

12

UPS12-150MR

-

9

17

25

UPS12-210MR

-

15

27

38

120kVA UPS

UPS12-100MR

-

-

5

9

UPS12-150MR

-

7

13

19

UPS12-210MR

-

11

21

31