UPS Specifications

36

5.4.2 DC Intermediate Circuit

See Table 8 for current ratings.

5.4.3 Inverter Output

See Table 8 for current ratings.

5.4.4 Bypass Input

Table 12

DC intermediate circuit

Rated Power kVA

40

60

80

100

120

Recommended number of lead-acid batteries

Total 40 battery blocks of 12VDC (240 cells of 2VDC)

will be supported by UPS

Recommended float charge voltage

2.27VDC *

Recommended boost charge voltage

2.4VDC *

Recommended end of discharge voltage

1.67 - 1.75 VDC

Maximum recharge battery current, A *

14.8

22.2

29.6

37.0

44.4

Maximum boost charge duration, min. *

1800

Boost-float threshold current, A *

0.1 C default

Temperature voltage compensation, mV/°C *

From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.*

Ripple voltage superimposed %

≤ 1

* Set by configuration software and based on usage of VLRA batteries.

Table 13

Inverter output

Rated Power kVA

40

60

80

100

120

Rated voltage, VAC

480

Supply

3-phase, 3-wire plus ground

Frequency, Hz

60 (50Hz in frequency converter mode)

Rated Power, kW

36

54

72

90

108

Three-phase transient overload,

min. load

105% to 110% for 60 minutes

111% to 125% for 10 minutes

126% to 150% for 1 minute

Voltage Regulation %

±1.0% three-phase RMS average for a balanced three-phase load

±2.0% three-phase RMS average for a 100% unbalanced load

Frequency Regulation %

Nominal frequency regulation is ±0.05% in single module mode,

and+/- 0.25% in parallel mode.

Maximum rate of change

of frequency, Hz/sec

For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s

Table 14

Bypass input

Rated Power, kVA

40

60

80

100

120

Rated voltage, VAC

480

Supply

Three-phase, 3-wire plus ground

Bypass voltage tolerance %

Upper limit: +10%, +15% or +20%; Upper limit default: +15%

Lower limit: -10%, -20%, -30% or -40%; Lower limit default: -20%

Frequency, Hz

60

Input frequency tolerance %

±2.5%, ±5%, ±10% and ±20%; default ±10%

Bypass overload capacity

(all ratings)

Time

Long-term operation:

10 minutes:

100 milliseconds:

Load
<135% load

135% - 170% load

1000% full UPS rated output current

See Table 8 for current ratings.